Series 6000

LEGIOMIX®, Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.

LEGIOMIX®, Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.
LEGIOMIX®, Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.
LEGIOMIX®, Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.
LEGIOMIX®, Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.
LEGIOMIX®, Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.
LEGIOMIX®, Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.
Download high resolution

Product Description

Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union.
Female threaded mixed connection.
Complete with:
- three-way ball valve;
- actuator;
- regulator;
- flow temperature probe;
- return temperature probe.
PATENT

Technical data

Auxiliary Microswitch: 1
Electrical Components: Yes
Material: brass
Protection class: IP 65 (actuator)
Running power consumption: (6,5+6) VA
Electric supply: 230 V AC
Disinfection temperature range: 40–85 °C
Adjustment temperature range: 20–85 °C
Medium temperature range: 5–100 °C
Maximum working pressure: 10 bar

Certifications

CE
ACS
HY-CERT
PZH

Drawings and specifications

Part number Connection Kv Actions
600051 R 3/4" (EN 10226-1) M
union
8,4 m³/h
2D drawings
3D models
Tender text
CALEFFI, 600051, LEGIOMIX®. Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union. With auxiliary microswitch. Female threaded mixed connection. Complete with: - three-way ball valve; - actuator; - regulator; - flow temperature probe; - return temperature probe. Connection: R 3/4" (EN 10226-1) M, union. Maximum working pressure: 10 bar. Medium temperature range: 5–100 °C. Adjustment temperature range: 20–85 °C. Disinfection temperature range: 40–85 °C. Electric supply: 230 V AC. Running power consumption: (6,5+6) VA. Protection class: IP 65 (actuator). Kv: 8,4 m³/h. Material: brass.
SCIP code
430a5eb6-9d70-48e1-8591-18de682cd944
600061 R 1" (EN 10226-1) M
union
10,6 m³/h
2D drawings
3D models
Tender text
CALEFFI, 600061, LEGIOMIX®. Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union. With auxiliary microswitch. Female threaded mixed connection. Complete with: - three-way ball valve; - actuator; - regulator; - flow temperature probe; - return temperature probe. Connection: R 1" (EN 10226-1) M, union. Maximum working pressure: 10 bar. Medium temperature range: 5–100 °C. Adjustment temperature range: 20–85 °C. Disinfection temperature range: 40–85 °C. Electric supply: 230 V AC. Running power consumption: (6,5+6) VA. Protection class: IP 65 (actuator). Kv: 10,6 m³/h. Material: brass.
SCIP code
3af48c40-eecd-44ac-b479-90d305fd22a0
600071 R 1 1/4" (EN 10226-1) M
union
21,2 m³/h
2D drawings
3D models
Tender text
CALEFFI, 600071, LEGIOMIX®. Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union. With auxiliary microswitch. Female threaded mixed connection. Complete with: - three-way ball valve; - actuator; - regulator; - flow temperature probe; - return temperature probe. Connection: R 1 1/4" (EN 10226-1) M, union. Maximum working pressure: 10 bar. Medium temperature range: 5–100 °C. Adjustment temperature range: 20–85 °C. Disinfection temperature range: 40–85 °C. Electric supply: 230 V AC. Running power consumption: (6,5+6) VA. Protection class: IP 65 (actuator). Kv: 21,2 m³/h. Material: brass.
SCIP code
c9a17e91-bf83-4b06-b596-2e64aa71dd56
600081 R 1 1/2" (EN 10226-1) M
union
32,5 m³/h
2D drawings
3D models
Tender text
CALEFFI, 600081, LEGIOMIX®. Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union. With auxiliary microswitch. Female threaded mixed connection. Complete with: - three-way ball valve; - actuator; - regulator; - flow temperature probe; - return temperature probe. Connection: R 1 1/2" (EN 10226-1) M, union. Maximum working pressure: 10 bar. Medium temperature range: 5–100 °C. Adjustment temperature range: 20–85 °C. Disinfection temperature range: 40–85 °C. Electric supply: 230 V AC. Running power consumption: (6,5+6) VA. Protection class: IP 65 (actuator). Kv: 32,5 m³/h. Material: brass.
SCIP code
8a2fcea6-1345-4ba2-852f-33efaea31799
600091 R 2" (EN 10226-1) M
union
41,0 m³/h
2D drawings
3D models
Tender text
CALEFFI, 600091, LEGIOMIX®. Electronic mixing valve with programmable thermal disinfection and check on disinfection, 230 V. Male threaded connections with union. With auxiliary microswitch. Female threaded mixed connection. Complete with: - three-way ball valve; - actuator; - regulator; - flow temperature probe; - return temperature probe. Connection: R 2" (EN 10226-1) M, union. Maximum working pressure: 10 bar. Medium temperature range: 5–100 °C. Adjustment temperature range: 20–85 °C. Disinfection temperature range: 40–85 °C. Electric supply: 230 V AC. Running power consumption: (6,5+6) VA. Protection class: IP 65 (actuator). Kv: 41,0 m³/h. Material: brass.
SCIP code
420b8619-b8e6-415e-aa64-5b99d5d783c0

Applications

Pipe Sizer Caleffi

This application allows for sizing and making calculations for pipes and conduits carrying water or air, respectively for hydraulic or aeraulic plants.

Caleffi Domestic Water Sizer allows fast and correct sizing of the main components of domestic water systems.