ThermoSetter™ Thermal Balancing Valve
Description:
Adjustable thermal balancing valve for domestic hot water recirculation circuits.
Body has section for thermal disinfection catridge retrofit.
Available with optional NA108 isolation valves (add "...001" to code suffix).
DZR low-lead brass valve body.
Drywell for temperature gauge or probe.
Optional outlet temperature gauge.
Optional check valve.
Max working pressure: 230 psi (16 bar)
Max differential presure: 14.5 psi (1 bar)
Max inlet temp: 195°F
Temp adjustment range: 95° - 140°F (35°- 60°C)
Cv max: 2.1
Cv min: 0.23
Cv design: 0.52
Compliance with the following standards:
NSF/ANSI/CAN 61 - Drinking Water System Component – Health Effects
NSF/ANSI 372 - Drinking Water System Components - Lead Content
Reduction of Lead in Drinking Water Act - California Health and
Safety Code 116875
S.3874 - Reduction of Lead in Drinking Water Act
Vermont Act 193 - The Lead in Plumbing Supplies Law
Maryland's Lead Free Law Hb.372
Downloads
Certifications:
Drawings:
code | connection | inlet check valve | gauge | weight (lbs) |
116140A |
½" NPT female |
no | no | 1.6 |
116140AC | ½" NPT female | yes | no | 1.8 |
116141A | ½" NPT female | no | yes | 1.7 |
116141AC | ½" NPT female | yes | yes | 1.9 |
116150A |
¾" NPT female |
no | no | 1.5 |
116150AC | ¾" NPT female | yes | no | 1.7 |
116151A |
¾" NPT female | no | yes | 1.6 |
116151AC |
¾" NPT female |
yes | yes | 1.8 |
116160A |
1" NPT female |
no | no | 2.1 |
116160AC |
1" NPT female |
yes | no | 2.3 |
116161A |
1" NPT female |
no | yes | 2.2 |
116161AC |
1" NPT female |
yes | yes |
2.4 |
116170A |
1¼" NPT female |
no | no | 1.8 |
116170AC |
1¼" NPT female |
yes | no | 1.8 |
116171A |
1¼" NPT female |
no | yes | 1.8 |
116171AC |
1¼" NPT female |
yes | yes | 1.8 |