PLURIMOD® EASY, Compact pre-assembled user module for heating and cooling systems (*).
Product Description
Compact pre-assembled user module for heating and cooling systems (*).
Complete with:
- strainer cartrdige with stainless steel mesh;
- fixed setting pressure differential control valve;
- 2 way zone valve with presetting;
- thermoelectric actuator with auxiliary microswitch;
- CONTECA® EASY (24 V AC) heat meter with turbine flow meter.
Reversible installation for primary side on left-hand (factory setting) or right-hand side.
Can be integrated with additional configuration options, to be ordered concurrently (*).
Technical data
Note
(*) Available configuration options:
- Cooling metering option (cod. 755810);
- MODBUS-RTU transmission option (cod. 750811);
- Flow rate scanning software option for DHW recirculation (cod. 755826);
- Couple of 8 m temperature probes (cod. 750931).
Services and Connectivity
Certifications
Download
Drawings and specifications
| Part number | Electric supply | Maximum recommended flow rate | Differential pressure fixed setting |
|---|---|---|---|
| 700213 | 230 V AC | 900 l/h | 20 kPa |
|
2D drawings
Tender text
CALEFFI, 700213, PLURIMOD® EASY.
Compact pre-assembled user module for heating and cooling systems (*).
Complete with:
- strainer cartrdige with stainless steel mesh;
- fixed setting pressure differential control valve;
- 2 way zone valve with presetting;
- thermoelectric actuator with auxiliary microswitch;
- CONTECA® EASY (24 V AC) heat meter with turbine flow meter.
Reversible installation for primary side on left-hand (factory setting) or right-hand side.
Can be integrated with additional configuration options, to be ordered concurrently (*). Medium temperature range: 3–90 °C. Differential pressure fixed setting: 20 kPa. Electric supply: 230 V AC. Nominal pressure: PN 10. Maximum recommended flow rate: 900 l/h.
SCIP code
d9bb5170-c404-4947-9109-9bb6be2707ba
|
|||
| 700214 | 24 V AC | 900 l/h | 20 kPa |
|
2D drawings
Tender text
CALEFFI, 700214, PLURIMOD® EASY.
Compact pre-assembled user module for heating and cooling systems (*).
Complete with:
- strainer cartrdige with stainless steel mesh;
- fixed setting pressure differential control valve;
- 2 way zone valve with presetting;
- thermoelectric actuator with auxiliary microswitch;
- CONTECA® EASY (24 V AC) heat meter with turbine flow meter.
Reversible installation for primary side on left-hand (factory setting) or right-hand side.
Can be integrated with additional configuration options, to be ordered concurrently (*). Medium temperature range: 3–90 °C. Differential pressure fixed setting: 20 kPa. Electric supply: 24 V AC. Nominal pressure: PN 10. Maximum recommended flow rate: 900 l/h.
SCIP code
492732ad-2b48-4c65-9e60-cc42afc8735f
|
|||
| 700215 | 230 V AC | 1400 l/h | 30 kPa |
|
2D drawings
3D models
Tender text
CALEFFI, 700215, PLURIMOD® EASY.
Compact pre-assembled user module for heating and cooling systems (*).
Complete with:
- strainer cartrdige with stainless steel mesh;
- fixed setting pressure differential control valve;
- 2 way zone valve with presetting;
- thermoelectric actuator with auxiliary microswitch;
- CONTECA® EASY (24 V AC) heat meter with turbine flow meter.
Reversible installation for primary side on left-hand (factory setting) or right-hand side.
Can be integrated with additional configuration options, to be ordered concurrently (*). Medium temperature range: 3–90 °C. Differential pressure fixed setting: 30 kPa. Electric supply: 230 V AC. Nominal pressure: PN 10. Maximum recommended flow rate: 1400 l/h.
SCIP code
82b90889-00db-44b6-a9f4-b8a9c47fbca5
|
|||
| 700216 | 24 V AC | 1400 l/h | 30 kPa |
|
2D drawings
Tender text
CALEFFI, 700216, PLURIMOD® EASY.
Compact pre-assembled user module for heating and cooling systems (*).
Complete with:
- strainer cartrdige with stainless steel mesh;
- fixed setting pressure differential control valve;
- 2 way zone valve with presetting;
- thermoelectric actuator with auxiliary microswitch;
- CONTECA® EASY (24 V AC) heat meter with turbine flow meter.
Reversible installation for primary side on left-hand (factory setting) or right-hand side.
Can be integrated with additional configuration options, to be ordered concurrently (*). Medium temperature range: 3–90 °C. Differential pressure fixed setting: 30 kPa. Electric supply: 24 V AC. Nominal pressure: PN 10. Maximum recommended flow rate: 1400 l/h.
SCIP code
ac6e17bd-3892-4fd5-ae55-022c0bad889c
|
|||