Kirill, We get this question from time to time. If the separator and pipe sizing is correct, because of the larger barrell in the separator, there is little to no pressure drop so distance from the separator to pipe elbow does not affect the performance. Your installation with an elbow 2X the pipe diameter from a flange or press fitting will be not affect the performance.