FLOWMATIC®, Pressure independent control valve.
Product Description
Pressure independent control valve.
Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports.
Technical data
Maximum working pressure:
16 bar, 25 bar
Medium temperature range:
-20–120 °C
Maximum percentage of glycol:
50 %
Medium:
water, glycol solutions
Range △p:
25–400 kPa
Material:
dezincification resistant brass DR
Download
Drawings and specifications
Part number | Connection | DN | Flow rate regulation range |
---|---|---|---|
145437 H20 | G 1/2" A (ISO 228-1) M |
DN 15 (body) | 0,02–0,20 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 1/2" A (ISO 228-1) M. Maximum working pressure: 16 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 15 (body). Flow rate regulation range: 0,02–0,20 m³/h. Material: dezincification resistant brass DR.
SCIP code
9d0688fc-7f74-422d-9443-383982108ad4
|
|||
145447 H40 | G 3/4" A (ISO 228-1) M |
DN 15 (body) | 0,08–0,40 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 3/4" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 15 (body). Flow rate regulation range: 0,08–0,40 m³/h. Material: dezincification resistant brass DR.
SCIP code
e5a23077-7663-43f4-aa72-139feb45b8de
|
|||
145447 H80 | G 3/4" A (ISO 228-1) M |
DN 15 (body) | 0,08–0,80 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 3/4" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 15 (body). Flow rate regulation range: 0,08–0,80 m³/h. Material: dezincification resistant brass DR.
SCIP code
c0d5a671-c017-4f53-8a0b-f3cf3d1531e2
|
|||
145557 H40 | G 1" A (ISO 228-1) M |
DN 20 (body) | 0,08–0,40 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 1" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 20 (body). Flow rate regulation range: 0,08–0,40 m³/h. Material: dezincification resistant brass DR.
SCIP code
8c29c94d-2401-4489-acf0-df62607f000a
|
|||
145557 H80 | G 1" A (ISO 228-1) M |
DN 20 (body) | 0,08–0,80 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 1" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 20 (body). Flow rate regulation range: 0,08–0,80 m³/h. Material: dezincification resistant brass DR.
SCIP code
e3424ac5-010b-403f-88d4-70c249d1f378
|
|||
145557 1H2 | G 1" A (ISO 228-1) M |
DN 20 (body) | 0,12–1,20 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 1" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 20 (body). Flow rate regulation range: 0,12–1,20 m³/h. Material: dezincification resistant brass DR.
SCIP code
35448a61-f144-488a-9c86-cadfd3b34c05
|
|||
145667 1H8 | G 1 1/4" A (ISO 228-1) M |
DN 25 (body) | 0,18–1,80 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 1 1/4" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 25 (body). Flow rate regulation range: 0,18–1,80 m³/h. Material: dezincification resistant brass DR.
SCIP code
35cc411e-92ac-4af0-89a9-c223f99999db
|
|||
145667 3H0 | G 1 1/4" A (ISO 228-1) M |
DN 25 (body) | 0,30–3,00 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 1 1/4" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 25 (body). Flow rate regulation range: 0,30–3,00 m³/h. Material: dezincification resistant brass DR.
SCIP code
af27a04b-6271-4a69-8e3e-ed856370e509
|
|||
145667 3H7 | G 1 1/4" A (ISO 228-1) M |
DN 25 (body) | 0,37–3,70 m³/h |
2D drawings
3D models
Tender text
Pressure independent control valve. Fitted for 145 series actuator and 6565/6566 series thermo-electric actuator.
Flow rate regulator in polymer with membrane in EPDM.
Graduated scale indicator.
With pressure test ports. Connection: G 1 1/4" A (ISO 228-1) M. Maximum working pressure: 25 bar. Medium temperature range: -20–120 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 25–400 kPa. DN: DN 25 (body). Flow rate regulation range: 0,37–3,70 m³/h. Material: dezincification resistant brass DR.
SCIP code