Good morning. Yes, the thermostatic head in vertical position is affected by the radiator emission and it would close before the room temperature reaches the set value. If you need a vertical installation, you can use the remote sensor version of the same head (201 series) so that you can position the sensor far from the radiator itself to correctly control the ambient temperature.
We hope this helps.