Balancing valve with flow meter and direct reading of flow rate.
Product Description
Balancing valve with flow meter and direct reading of flow rate.
Graduated scale flow meter with magnetic movement flow rate indicator.
Brass flow meter.
To be coupled with flat counterflanges EN 1092-1.
PATENT
Technical data
Maximum working pressure:
10 bar
Medium temperature range:
-10–110 °C
Maximum percentage of glycol:
50 %
Medium:
water, glycol solutions
Material:
cast iron
Download
Drawings and specifications
Part number | Connection | Flow rate regulation range | |
---|---|---|---|
132060 | DN 65 (EN 1092-1) PN 16 |
6–24 m³/h | |
3D models
Tender text
Balancing valve with flow meter and direct reading of flow rate.
Graduated scale flow meter with magnetic movement flow rate indicator.
Brass flow meter.
To be coupled with flat counterflanges EN 1092-1.
Connection: DN 65 (EN 1092-1) PN 16. Maximum working pressure: 10 bar. Medium temperature range: -10–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Flow rate regulation range: 6–24 m³/h. Material: cast iron.
SCIP code
cb753e9f-0218-47fb-85d5-a048c3c408ee
|
|||
132080 | DN 80 (EN 1092-1) PN 16 |
8–32 m³/h | |
3D models
Tender text
Balancing valve with flow meter and direct reading of flow rate.
Graduated scale flow meter with magnetic movement flow rate indicator.
Brass flow meter.
To be coupled with flat counterflanges EN 1092-1.
Connection: DN 80 (EN 1092-1) PN 16. Maximum working pressure: 10 bar. Medium temperature range: -10–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Flow rate regulation range: 8–32 m³/h. Material: cast iron.
SCIP code
80cd2dc8-7d5f-4126-b3ba-28c08727e9d3
|
|||
132100 | DN 100 (EN 1092-1) PN 16 |
12–48 m³/h | |
3D models
Tender text
Balancing valve with flow meter and direct reading of flow rate.
Graduated scale flow meter with magnetic movement flow rate indicator.
Brass flow meter.
To be coupled with flat counterflanges EN 1092-1.
Connection: DN 100 (EN 1092-1) PN 16. Maximum working pressure: 10 bar. Medium temperature range: -10–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Flow rate regulation range: 12–48 m³/h.
SCIP code
467b3baa-3b40-47dc-9fa8-a36d00f9e95e
|