Gas pressure closing regulator, double diaphragm. Flanged connections.
Product Description
Gas pressure closing regulator, double diaphragm. Flanged connections.
To be coupled with flat counterflanges EN 1092-1.
Compliance with directive ATEX (II 2G - II 2D).
Regulation and closing at null flow according to UNI EN 88.
Technical data
Maximum upstream pressure:
500 mbar
Medium temperature range:
-15–60 °C
Certifications


Download
Drawings and specifications
Part number | Connection | Adjustment pressure range | |
---|---|---|---|
852060 | DN 65 (EN 1092-1) PN 16 |
13–27 mbar | |
3D models
Tender text
Gas pressure closing regulator, double diaphragm. Flanged connections.
To be coupled with flat counterflanges EN 1092-1. Compliance with directive ATEX (II 2G - II 2D).
Regulation and closing at null flow according to UNI EN 88. Connection: DN 65 (EN 1092-1) PN 16. Maximum upstream pressure: 500 mbar. Medium temperature range: -15–60 °C. Adjustment pressure range: 13–27 mbar.
SCIP code
3675bfb8-8677-4ea7-bb72-f94ab1329546
|
|||
852080 | DN 80 (EN 1092-1) PN 16 |
13–27 mbar | |
3D models
Tender text
Gas pressure closing regulator, double diaphragm. Flanged connections.
To be coupled with flat counterflanges EN 1092-1. Compliance with directive ATEX (II 2G - II 2D).
Regulation and closing at null flow according to UNI EN 88. Connection: DN 80 (EN 1092-1) PN 16. Maximum upstream pressure: 500 mbar. Medium temperature range: -15–60 °C. Adjustment pressure range: 13–27 mbar.
SCIP code
3675bfb8-8677-4ea7-bb72-f94ab1329546
|
|||
852100 | DN 100 (EN 1092-1) PN 16 |
15–27 mbar | |
3D models
Tender text
Gas pressure closing regulator, double diaphragm. Flanged connections.
To be coupled with flat counterflanges EN 1092-1. Compliance with directive ATEX (II 2G - II 2D).
Regulation and closing at null flow according to UNI EN 88. Connection: DN 100 (EN 1092-1) PN 16. Maximum upstream pressure: 500 mbar. Medium temperature range: -15–60 °C. Adjustment pressure range: 15–27 mbar.
SCIP code
3675bfb8-8677-4ea7-bb72-f94ab1329546
|