Automatic flow rate regulator with high-performance tecnopolymer cartridge.
Fitted for connection of pressure ports and drain valve.
Accuracy: ± 10 %. Flow rates: 0,085–11,0 m3/h.
PATENT

Technical data

Maximum percentage of glycol: 50 %
Medium: water, glycol solutions
Material: dezincification resistant brass DR
Range △p: 15–200 kPa
Medium temperature range: -20–100 °C
Maximum working pressure: 25 bar

Note

Minimum differential pressure required 
This is given by the sum of two values: 

  1. the minimum working Δp of the AUTOFLOW cartridge; 
  2.  the Δp required for the nominal flow rate to pass through the valve body. This value can be determined on the basis of the values of Kv shown above referring to the valve body. 

Pump head H = Δpcircuit + Δprequise 

Drawings and specifications

Part number Connection Note Kv
2D drawings
Download
Download
3D models
Tender text
CALEFFI, 126141***, AUTOFLOW®. Automatic flow rate regulator with high-performance tecnopolymer cartridge. Fitted for connection of pressure ports and drain valve. Accuracy: ± 10 %. Flow rates: 0,085–11,0 m3/h. Connection: G 1/2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: -20–100 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 15–200 kPa. Kv: 6,69 m³/h. Material: dezincification resistant brass DR.
2D drawings
Download
Download
3D models
Tender text
CALEFFI, 126151***, AUTOFLOW®. Automatic flow rate regulator with high-performance tecnopolymer cartridge. Fitted for connection of pressure ports and drain valve. Accuracy: ± 10 %. Flow rates: 0,085–11,0 m3/h. Connection: G 3/4" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: -20–100 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 15–200 kPa. Kv: 7,58 m³/h. Material: dezincification resistant brass DR.
2D drawings
Download
Download
3D models
Tender text
CALEFFI, 126161***, AUTOFLOW®. Automatic flow rate regulator with high-performance tecnopolymer cartridge. Fitted for connection of pressure ports and drain valve. Accuracy: ± 10 %. Flow rates: 0,085–11,0 m3/h. Connection: G 1" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: -20–100 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 15–200 kPa. Kv: 14,00 m³/h. Material: dezincification resistant brass DR.
2D drawings
Download
Download
3D models
Download
Download
Tender text
CALEFFI, 126171***, AUTOFLOW®. Automatic flow rate regulator with high-performance tecnopolymer cartridge. Fitted for connection of pressure ports and drain valve. Accuracy: ± 10 %. Flow rates: 0,085–11,0 m3/h. Connection: G 1 1/4" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: -20–100 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 15–200 kPa. Kv: 14,50 m³/h. Material: dezincification resistant brass DR.
2D drawings
Download
Download
3D models
Tender text
CALEFFI, 126181***, AUTOFLOW®. Automatic flow rate regulator with high-performance tecnopolymer cartridge. Fitted for connection of pressure ports and drain valve. Accuracy: ± 10 %. Flow rates: 0,085–11,0 m3/h. Connection: G 1 1/2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: -20–100 °C. Maximum percentage of glycol: 50 %. Medium: glycol solutions. Range △p: 15–200 kPa. Kv: 34,72 m³/h. Material: dezincification resistant brass DR.
2D drawings
Download
Download
3D models
Tender text
CALEFFI, 126191***, AUTOFLOW®. Automatic flow rate regulator with high-performance tecnopolymer cartridge. Fitted for connection of pressure ports and drain valve. Accuracy: ± 10 %. Flow rates: 0,085–11,0 m3/h. Connection: G 2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: -20–100 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Range △p: 15–200 kPa. Kv: 37,38 m³/h. Material: dezincification resistant brass DR.

Applications

Pipe Sizer Caleffi
Pipe Sizer Caleffi

This application allows for sizing and making calculations for pipes and conduits carrying water or air, respectively for hydraulic or aeraulic plants.