Series 167

Motorised regulating unit DN 32, for heating and cooling systems.

167662he4.png
167662he4.png
Download high resolution

Product Description

Motorised regulating unit DN 32, for heating and cooling systems.
Right - left convertible.
Available with three-point control signal actuator (note A) or 0(2)–10V control signal and 0–10V feedback signal (note B).
Regulation with three-way sector valve.
With insulation.

Technical data

Type of pump: Para 25-9
Main centre distance: 125 mm
Medium temperature range: 5–100 °C
Maximum working pressure: 10 bar

Note

Note A: three-point control signal actuator.
Operating time: 150 s.
Can be combined with regulators code 161010 and 1520 series.

Note B: 0(2)–10 V control signal actuator.
Feedback signal: 0–10 V.
Operating time: 75 s.
Can be combined with regulator code 161010 (for actuator electic supply use 230V / 24V transformer).

Certifications

CE

Drawings and specifications

Part number System side connection Boiler side connection Note Actions
167662HE4 G 1 1/4" (ISO 228-1) F
G 1 1/2" A (ISO 228-1) M
A
Electric supply
230 V AC
Flow rate with available head 4 m w.g.
2,2 m³/h
2D drawings
Download
Download
3D models
Download
Download
Tender text
CALEFFI, 167662HE4. Motorised regulating unit DN 32, for heating and cooling systems. With insulation. With auxiliary microswitch. Right - left convertible. Available with three-point control signal actuator (note A) or 0(2)–10V control signal and 0–10V feedback signal (note B). Regulation with three-way sector valve. System side connection: G 1 1/4" (ISO 228-1) F. Boiler side connection: G 1 1/2" A (ISO 228-1) M. Maximum working pressure: 10 bar. Medium temperature range: 5–100 °C. Electric supply: 230 V AC. Main centre distance: 125 mm. Flow rate with available head 4 m w.g.: 2,2 m³/h. Type of pump: Para 25-9.
SCIP code
375fe02e-d029-4738-a96c-7828eac8c7d7
167664HE4 G 1 1/4" (ISO 228-1) F
end outlet
G 1 1/2" A (ISO 228-1) M
B
Electric supply
24 V AC
Flow rate with available head 4 m w.g.
2,2 m³/h
2D drawings
Download
Download
3D models
Download
Download
Tender text
CALEFFI, 167664HE4. Motorised regulating unit DN 32, for heating and cooling systems. With insulation. With auxiliary microswitch. Right - left convertible. Available with three-point control signal actuator (note A) or 0(2)–10V control signal and 0–10V feedback signal (note B). Regulation with three-way sector valve. System side connection: G 1 1/4" (ISO 228-1) F, end outlet. Boiler side connection: G 1 1/2" A (ISO 228-1) M. Maximum working pressure: 10 bar. Medium temperature range: 5–100 °C. Electric supply: 24 V AC. Main centre distance: 125 mm. Flow rate with available head 4 m w.g.: 2,2 m³/h. Type of pump: Para 25-9.
SCIP code
e14c9fcb-10ce-4ca0-99e5-c101423be3e1

Applications

Pipe Sizer Caleffi
Pipe Sizer Caleffi

This application allows for sizing and making calculations for pipes and conduits carrying water or air, respectively for hydraulic or aeraulic plants.