AUTOFLOW®, Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Product Description
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection.
Technical data
Material:
dezincification resistant brass DR , dezincification resistant brass DR
Medium:
water, glycol solutions
Maximum percentage of glycol:
50 %
Medium temperature range:
0–110 °C
Maximum working pressure:
25 bar
Note
Minimum differential pressure required
This is given by the sum of two values:
- the minimum working Δp of the AUTOFLOW cartridge;
- the Δp required for the nominal flow rate to pass through the valve body. This value can be determined on the basis of the values of Kv shown above referring to the valve body.
Pump head H = Δpcircuit + Δprequise
Download
Drawings and specifications
| Part number | Connection | Note | Kv |
|---|---|---|---|
| 120141*** (10–95 kPa) | G 1/2" (ISO 228-1) F |
0,3; 0,45; 0,5; 0,6; 0,7; 0,8; 0,9; 1,0 | 6,9 m³/h |
|
2D drawings
Tender text
CALEFFI, 120141*** (10–95 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1/2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: glycol solutions. Kv: 6,9 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120151*** (10–95 kPa) | G 3/4" (ISO 228-1) F |
0,3; 0,45; 0,5; 0,6; 0,7; 0,8; 0,9; 1,0 | 7,73 m³/h |
|
Tender text
CALEFFI, 120151*** (10–95 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 3/4" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Kv: 7,73 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120161*** (10–95 kPa) | G 1" (ISO 228-1) F |
0,7; 0,8; 0,9; 1,0 | 17,04 m³/h |
|
2D drawings
Tender text
CALEFFI, 120161*** (10–95 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Kv: 17,04 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120171*** (10–95 kPa) | G 1 1/4" (ISO 228-1) F |
0,7; 0,8; 0,9; 1,0 | 17,74 m³/h |
|
3D models
Tender text
CALEFFI, 120171*** (10–95 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1 1/4" (ISO 228-1) F. Kv: 17,74 m³/h.
|
|||
| 120181*** (10–95 kPa) | G 1 1/2" (ISO 228-1) F |
2,75; 3,0; 3,25; 3,5; 3,75; 4,25; 5,0; 7,0 | $$ data missing $$ |
|
3D models
Tender text
CALEFFI, 120181*** (10–95 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1 1/2" (ISO 228-1) F.
|
|||
| 120191*** (10–95 kPa) | G 2" (ISO 228-1) F |
2,75; 3,0; 3,25; 3,5; 3,75; 4,25; 5,0; 7,0 | $$ data missing $$ |
|
2D drawings
3D models
Tender text
CALEFFI, 120191*** (10–95 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 2" (ISO 228-1) F.
|
|||
| 120141*** (22–210 kPa) | G 1/2" (ISO 228-1) F |
0,12; 0,15; 0,2; 0,25; 0,35; 0,4; 0,6; 0,7; 0,8; 0,9; 1,2; 1,4; 1,6; 1,8 | 6,90 m³/h |
|
2D drawings
Tender text
CALEFFI, 120141*** (22–210 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1/2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: glycol solutions. Kv: 6,90 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120151*** (22–210 kPa) | G 3/4" (ISO 228-1) F |
0,12; 0,15; 0,2; 0,25; 0,35; 0,4; 0,6; 0,7; 0,8; 0,9; 1,2; 1,4; 1,6; 1,8 | 7,73 m³/h |
|
Tender text
CALEFFI, 120151*** (22–210 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 3/4" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Kv: 7,73 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120161*** (22–210 kPa) | G 1" (ISO 228-1) F |
1,0; 1,2; 1,4; 1,6; 1,8; 2,0; 2,25; 2,5; 2,75; 3,0; 3,25; 3,5; 3,75; 4,0; 4,25 | 17,04 m³/h |
|
2D drawings
Tender text
CALEFFI, 120161*** (22–210 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1" (ISO 228-1) F.
|
|||
| 120171*** (22–210 kPa) | G 1 1/4" (ISO 228-1) F |
1,0; 1,2; 1,4; 1,6; 1,8; 2,0; 2,25; 2,5; 2,75; 3,0; 3,25; 3,5; 3,75; 4,0; 4,25 | 17,74 m³/h |
|
2D drawings
Tender text
CALEFFI, 120171*** (22–210 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1 1/4" (ISO 228-1) F.
|
|||
| 120181*** (22–210 kPa) | G 1 1/2" (ISO 228-1) F |
4,0; 4,5; 5,5; 6,0; 6,5; 7,5; 8,0; 8,5; 9,0; 9,5; 10,0; 11,0 | 47,24 m³/h |
|
Tender text
CALEFFI, 120181*** (22–210 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1 1/2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: glycol solutions. Kv: 47,24 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120191*** (22–210 kPa) | G 2" (ISO 228-1) F |
4,0; 4,5; 5,5; 6,0; 6,5; 7,5; 8,0; 8,5; 9,0; 9,5; 10,0; 11,0 | 48,89 m³/h |
|
2D drawings
Tender text
CALEFFI, 120191*** (22–210 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Kv: 48,89 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120141*** (40–390 kPa) | G 1/2" (ISO 228-1) F |
0,25; 0,35; 0,45; 0,7; 0,9; 1,1; 1,4; 1,8; 2,1; 2,25; 2,75 | 6,90 m³/h |
|
2D drawings
Tender text
CALEFFI, 120141*** (40–390 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1/2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: glycol solutions. Kv: 6,90 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120151*** (40–390 kPa) | G 3/4" (ISO 228-1) F |
0,25; 0,35; 0,45; 0,7; 0,9; 1,1; 1,4; 1,8; 2,1; 2,25; 2,75 | 7,73 m³/h |
|
Tender text
CALEFFI, 120151*** (40–390 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 3/4" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Kv: 7,73 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120161*** (40–390 kPa) | G 1" (ISO 228-1) F |
1,6; 1,8; 2,1; 2,25; 2,5; 2,75; 3,0; 3,25; 3,5; 3,75; 4,0; 4,25; 4,5; 5,0; 5,5; 6,0 | 17,04 m³/h |
|
2D drawings
Tender text
CALEFFI, 120161*** (40–390 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: water, glycol solutions. Kv: 17,04 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120171*** (40–390 kPa) | G 1 1/4" (ISO 228-1) F |
1,6; 1,8; 2,1; 2,25; 2,5; 2,75; 3,0; 3,25; 3,5; 3,75; 4,0; 4,25; 4,5; 5,0; 5,5; 6,0 | 17,74 m³/h |
|
2D drawings
Tender text
CALEFFI, 120171*** (40–390 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1 1/4" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Medium: glycol solutions. Kv: 17,74 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120181*** (40–390 kPa) | G 1 1/2" (ISO 228-1) F |
3,0; 3,25; 3,5; 3,75; 4,0; 4,25; 4,5; 6,5; 7,0; 7,5; 8,0; 8,5; 9,0; 10,0; 11,0; 12,0; 13,0; 14,5; 15,5 | 47,24 m³/h |
|
Tender text
CALEFFI, 120181*** (40–390 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 1 1/2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Kv: 47,24 m³/h. Material: dezincification resistant brass DR.
|
|||
| 120191*** (40–390 kPa) | G 2" (ISO 228-1) F |
3,0; 3,25; 3,5; 3,75; 4,0; 4,25; 4,5; 6,5; 7,0; 7,5; 8,0; 8,5; 9,0; 10,0; 11,0; 12,0; 13,0; 14,5; 15,5 | 48,89 m³/h |
|
2D drawings
Tender text
CALEFFI, 120191*** (40–390 kPa), AUTOFLOW®.
Combination of automatic flow rate regulator, with stainless steel cartridge, and ball valve.
Accuracy: ± 5 %.
Designed for pressure point and drain valve connection. Connection: G 2" (ISO 228-1) F. Maximum working pressure: 25 bar. Medium temperature range: 0–110 °C. Maximum percentage of glycol: 50 %. Kv: 48,89 m³/h. Material: dezincification resistant brass DR.
|
|||