April 07, 2017

The 521 can be mounted in any orientation, no problem. Irregular water temperature could be caused by a number of factors. The 521 has a minimum flow rating of 1.3 GPM; flow rate less than that can cause valve "hunting" and irregular temperature fluctuations. Check valves on the hot and cold inlet are recommended to prevent cross-flow during pressure variations also. Make sure the hot water supply is delivering a good steady flow of water that is at least 25 degrees higher than the setpoint on the 521 knob.