SinkMixer™, 4-port scald protection point-of-use mixing valve
Product Description
4-port scald protection point-of-use mixing valve
Thermostatic mixing valve for under sink and under counter applications where the user must be protected from the danger of scalding caused by excessively hot water.
Cold inlet temperature: Min. 39°F; max. 85°F. Hot inlet temperature: Min. 120°F; max. 195°F.
Technical data
Adjustment temperature range:
95–120 °F
Flow rate working range:
0.35–2.3 gpm
Certifications
![ES LOW LEAD ES LOW LEAD](/sites/default/files/certifications/ICC%20ES%20PMG-LOW%20LEAD.jpg)
![Buy American Act Buy American Act](/sites/default/files/certifications/Buy-American-Act.png)
![California HSC 116875 California HSC 116875](/sites/default/files/certifications/California-HSC-116875.png)
![Maryland HB372 Maryland HB372](/sites/default/files/certifications/Maryland-HB372.png)
![United States S.3874 United States S.3874](/sites/default/files/certifications/United-States-S.3874.png)
![Vermont Act 193 Vermont Act 193](/sites/default/files/certifications/Vermont-Act-193-.png)
![NSF/ANSI/CAN 372 NSF/ANSI/CAN 372](/sites/default/files/certifications/NSF-ANSI-CAN-372.png)
![NSF/ANSI/CAN 61 NSF/ANSI/CAN 61](/sites/default/files/certifications/CAN-61.png)
![CSA B125.3 CSA B125.3](/sites/default/files/certifications/CSA-B125.3.png)
![ASME A112.1070 ASME A112.1070](/sites/default/files/certifications/ASME-A112.1070.png)
![ASSE 1070 ASSE 1070](/sites/default/files/certifications/ASSE1070.png)
![CSA B125.70 CSA B125.70](/sites/default/files/certifications/CSA-B125.70.png)
Download
Drawings and specifications
Part number | Connection | Note | Cv |
---|---|---|---|
521201A | 3/8" compression ends |
- | 0.52 |
2D drawings
3D models
Tender text
4-port scald protection point-of-use mixing valve
Thermostatic mixing valve for under sink and under counter applications where the user must be protected from the danger of scalding caused by excessively hot water.
Cold inlet temperature: Min. 39°F; max. 85°F. Hot inlet temperature: Min. 120°F; max. 195°F. Connection: 3/8", compression ends. Adjustment temperature range: 95–120 °F. Flow rate working range: 0.35–2.3 gpm. Cv: 0.52.
SCIP code
117ff071-348f-48c0-83d2-23b5c9fcbf52
|
|||
521201AP | 3/8" compression ends |
Plug/fittings | 0.52 |
3D models
Tender text
4-way scald protection point-of-use mixing valve
Thermostatic mixing valve for under sink and under counter applications where the user must be protected from the danger of scalding caused by excessively hot water.
Cold inlet temperature: Min. 39°F; max. 85°F. Hot inlet temperature: Min. 120°F; max. 195°F. Connection: 3/8", compression ends. Adjustment temperature range: 95–120 °F. Flow rate working range: 0.35–2.3 gpm. Cv: 0.52.
|