149

Connection and regulation kit for HVAC terminal units. Without Venturi device

Description: 

Connection and regulation kit for HVAC terminal units.
dezincification resistant alloy body.
Complete with:
- pressure independent control valve,
- three-way shut-off valve,
- integrated by-pass,
- strainer mesh,
- pre-formed shell insulation.

Max working pressure: 25 bar.
Temperature range: -10÷120 °C.
Maximum percentage of glycol: 50 %.
Dp Range (PICV): 25÷400 kPa.
Centre distance: 80 mm.
For actuators 145 series actuator and
6565/6566 series thermo-electric actuator.

Downloads

Drawings: 

3D cad

BIM model

Code

DN

Flow rate regulation range 

(m3/h)

Pack

Package

149410 H20

15

0,02÷0,20

1

-

149410 H40

15

0,08÷0,40

1

-

149410 H80

15

0,08÷0,80

1

-

149510 H20

20

0,02÷0,20

1

-

149510 H40

20

0,08÷0,40

1

-

149510 H80

20

0,08÷0,80

1

-

149510 1H2

20

0,12÷1,20

1

-

149610 1H8

25

0,18÷1,80

1

-

149610 3H0

25

0,30÷3,00

1

-

149610 3H7 

25

0,37–3,70 

1 -

 