149

Connection and regulation kit for HVAC terminal units

Description: 

Connection and regulation kit
for HVAC terminal units.
CR dezincification resistant alloy body.
Complete with:
- pressure independent control valve,
- three-way shut-off valve,
- filtering cartridge,
- integrated by-pass,
- Venturi device with pressure test ports,
- fill/drain cock.

Max. working pressure: 25 bar.
Temperature range: -10–120 °C.
Max. percentage of glycol: 50 %.
Δp range (PICV): 25–400 kPa.
Centre distance: 40 mm.
Fitted for 145 series actuator and
6565/6566 series thermo-electric actuator.

*Single installation code 149500 ... 001
**Double installation code 149500 ... 001+
code 149500 ... 002

Downloads

Drawings: 

Code

DN

KV Venturi
(m3/h) 

Flow rates 
range (m3/h)

Pack

Package

149500 H08 001*

20

0,15

0,02–0,08 

1

-

149500 H20 001*

20

0,50

0,08–0,20 

1

-

149500 H40 001*

20

1,10

0,20–0,40 

1

-

149500 H80 001* 

20

2,25

0,40–0,80 

1

-

149500 1H2 001* 

20

3,90

0,60–1,20 

1

-

149500 H08 002**

20

0,15

0,02–0,08 

1

-

149500 H20 002** 

20

0,50

0,08–0,20 

1

-

149500 H40 002**

20

1,10

0,20–0,40 

1

-

149500 H80 002**

20

2,25

0,40–0,80 

1

-

149500 1H2 002** 

20

3,90

0,60–1,20 

1

-

 

 

Related products